Electrical drawings: lesson 3 of 6

Device tags

Name the device from its tag. Get 10 right to finish.

Done 0 of 10
PB7

On a US control drawing, what is PB7?

Why tags matter

A coil and its contacts are often far apart on a drawing, even on different pages. The tag ties them together: every contact tagged CR2 opens or closes when coil CR2 is energized.

US drawings

TagDevice
CRControl relay
MMotor starter (contactor)
PBPushbutton
LSLimit switch
OLOverload relay
FUFuse
CBCircuit breaker
TRTime delay relay
TTransformer
SSSelector switch
PSPressure switch
PLPilot light

IEC drawings (IEC 81346-2)

IEC tags start with a dash, then a class letter and a number: -S1, -K3, -F2.

LetterClass
-SPushbutton or manual switch
-MMotor
-FProtective device (fuse or overload relay)
-KRelay
-TTransformer
-XTerminal

Two letters vary between drawings, so we do not test them: contactors appear as -K or -Q, and indicator lamps as -H (older practice) or -P (IEC 81346-2).

Questions

What does CR mean on a control drawing?
Control relay. CR1, CR2 and so on are separate relays. Their contacts carry the same tag as the coil.
Is a contactor -K or -Q on IEC drawings?
Both are used. IEC 81346-2 puts power-switching devices under Q, but many drawings tag contactors -K. Check the legend of your drawing set.

Explained in our own words and checked against several references. For the full rules, see the NEC (NFPA 70), NFPA 79, IEC 60617, IEC 60445 and IEC 81346-2. Your drawing legend always comes first.