Electrical drawings: lesson 5 of 6

Wire sizes: AWG and mm²

Compare gauges and convert sizes. Get 10 right to finish. US asks about AWG; IEC asks for the metric size.

Done 0 of 10
14 AWG

About how big is the copper cross-section of 14 AWG wire?

AWG counts backwards

US drawings give wire sizes in AWG (American Wire Gauge). The number comes from how many times the wire was drawn through a die, so a higher number means a thinner wire. European drawings give the copper cross-section in mm².

AWGArea (mm²)Diameter (mm)Next metric size up
161.311.291.5 mm²
142.081.632.5 mm²
123.312.054 mm²
105.262.596 mm²
88.373.2610 mm²
613.34.1216 mm²
421.25.1925 mm²

When you swap an AWG size for a metric one, go to the next size up, never down. The wire must carry at least as much current as the drawing asks for.

Questions

Is a higher AWG number thicker or thinner?
Thinner. 14 AWG is thinner than 12 AWG. Going down 3 gauge numbers roughly doubles the copper area.
What is 12 AWG in mm²?
About 3.31 mm². The next standard metric size up is 4 mm².

Explained in our own words and checked against several references. For the full rules, see the NEC (NFPA 70), NFPA 79, IEC 60617, IEC 60445 and IEC 81346-2. Your drawing legend always comes first.